Process Flow
IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 75
Details for GOOD (non-cascade)
128 80 1 0 0 0 0 0 = ok TB, AI, MV, PID
132 84 1 0 0 0 0 1 = active block
alarm
TB, AI, PID
136 88 1 0 0 0 1 0 = active advisory
alarm
AI, PID
140 8C 1 0 0 0 1 1 = active critical
alarm
AI, PID
144 90 1 0 0 1 0 0 = unacknowl-
edged block
alarm
AI, PID
148 94 1 0 0 1 0 1 = unacknowl-
edged advisory
alarm
AI, PID
152 98 1 0 0 1 1 0 = unacknowl-
edged critical
alarm
AI, PID
Active Block alarm detail:
Set when the value is Good and the block has an Active Block alarm.
Active advisory alarm detail:
Set when the value is Good and the block has an Active alarm with priority less than 8.
Active critical alarm detail:
Set when the value is Good and the block has an Active alarm with priority greater than or equal
to eight.
Unacknowledged Block alarm detail:
Set when the value is Good and the block has an unacknowledged Block alarm.
Unacknowledged advisory alarm detail:
Set when the value is Good and the block has an unacknowledged alarm with priority less
than 8.
Unacknowledged critical alarm detail:
Set when the value is Good and the block has an unacknowledged alarm with priority greater
than or equal to eight.